Presentasi sedang didownload. Silahkan tunggu

Presentasi sedang didownload. Silahkan tunggu

Konsep Asesmen Kondisi WG-2

Presentasi serupa


Presentasi berjudul: "Konsep Asesmen Kondisi WG-2"— Transcript presentasi:

1 Konsep Asesmen Kondisi WG-2
Working Group Switchgear Circuit Breaker (CB) Disconnecting Switch (DS)

2 Konsep Asesmen P3B JB

3 Condition Assessment (PMT & PMS)

4 Alur Desain asesmen kondisi PMT & PMS
W E I G H T N F A C O R W E I G H T N F A C O R Critical failure mode SS1 FMEA FMECA Inspeksi Level-1 SS2 SS3 Inspeksi Level-2 Indeks Kondisi 1,6,9 SS4 SS5 SS6 SS7 Asesmen Kondisi Adjustment weight Sense of engineering

5 FMECA Critical failure mode - PMT 500 kV
Risk = Effect x Probability detail Probability = frequency ; Effect = Safety + System + Environment + Cost

6 Asesmen Kondisi PMT X X X X X X X X X W E I G H T N F A C O R
Electrical Current Carrying (SS1) W E I G H T N F A C O R X Electrical Switching (SS2) X Electrical Insulation (SS3) X Hasil Inspeksi Level 1 X Indeks Kondisi PMT Driving Mechanism (SS4) X Control System (SS5) X Hasil Inspeksi level 2 X Mechanical Structure (SS6) X Grounding (SS7) X Dilakukan adjustment berdasarkan nilai criticality masing-masing failure mode (FMECA), sense of engineering

7 Perhitungan Indeks Kondisi PMT
PMT 500 kV = (0.04 x SS1)+(0.3 x SS2)+(0.33 x SS3)+(0.11 x SS4) +(0.19 x SS5)+(0.02 x SS6)+(0.01 x SS7) PMT 150 kV = (0.06 x SS1)+(0.16 x SS2)+(0.26 x SS3)+(0.20 x SS4) +(0.29 x SS5)+(0.02 x SS6)+(0.01 x SS7) PMT 70 kV = (0.07 x SS1)+(0.21 x SS2)+(0.29 x SS3)+(0.15 x SS4) +(0.25 x SS5)+(0.02 x SS6)+(0.01 x SS7) PMT 20 kV = (0.05 x SS1)+(0.15 x SS2)+(0.51 x SS3)+(0.11 x SS4) +(0.15 x SS5)+(0.02 x SS6)+(0.01 x SS7) Kategori : Baik = 7.5 – 9 Sedang = 5.5 – 7.49 Buruk = 0 – 5.49 detail

8 Asesmen Kondisi PMS X X X X X X X X X W E I G H T N F A C O R
Struktur mekanik (SS1) W E I G H T N F A C O R X Isolasi (SS2) X Bagian yang bertegangan (SS3) X Hasil Inspeksi Level 1 X Indeks Kondisi PMS Grounding (SS4) X Mekanik (SS5) X Hasil Inspeksi level 2 X Control & Auxiliary circuit (SS6) X Pisau pentanahan (SS7) X

9 Perhitungan Indeks Kondisi PMS
PMS 500 kV = (0.15 x SS1)+(0.18 x SS2)+(0.15 x SS3)+(0.10 x SS4) +(0.05 x SS5)+(0.15 x SS6)+(0.23 x SS7) PMS 150 kV = (0.15 x SS1)+(0.20 x SS2)+(0.29 x SS3)+(0.10 x SS4) +(0.10 x SS5)+(0.12 x SS6)+(0.05 x SS7) PMS 70 kV = (0.15 x SS1)+(0.20 x SS2)+(0.29 x SS3)+(0.10 x SS4) +(0.10 x SS5)+(0.12 x SS6)+(0.05 x SS7) Kategori : Baik = 7.5 – 9 Sedang = 5.5 – 7.49 Buruk = 0 – 5.49 detail

10 Progress WG SWITCHGEAR
Form Inspeksi Level-1 CB & DS Asesmen Kondisi CB dan DS Form Inspeksi Level-2 (tidak ada) Draft IK level-2 (tidak ada)

11 Terima kasih


Download ppt "Konsep Asesmen Kondisi WG-2"

Presentasi serupa


Iklan oleh Google