SISTIM VENTILASI PENGENCERAN UADAR STANDARD DESIN “ ASHRAE’S “ ETAPRIMA SAFETY ENGINEERING, M.ARIEFF.L Ir. LATAR MUH. ARIF , MSc
ASHRAE - American Society of Heating Regfrigerating and Air Contitioning Engineers PERSAMAAN VENTILASI Pengenceran udara panas MENGHTUNG kebutuhan udara segar/fresh air bagi karyawan MENGHTUNG berapa jumlah diffuser diperlukan MENGHTUNG berapa jumlah Exhaust dibutuhkan ETAPRIMA SAFETY ENGINEERING, M.ARIEFF.L
ETAPRIMA SAFETY ENGINEERING, M.ARIEFF.L
ASHARE SATANDAR, yang telah ditetapkan , Flowrate = 0.25 – 0.5 m/s atau (50 – 100) fpm Flowrate difusser : (50- 100) fpm ; Temperatur udara = 800F atau (24 – 26) 0C Kelembaban nisbi/relative humaddity = 30 – 50 % Ruang kerja = 4 m2/person Flowrate (Q) = 20 cfm/person Dimensi Diffuser (40 cm x 40 cm ) x 20 % Standar exhaust : (20 cm x 20 cm ) x 50 % Jam kerja : 8 jam /hari Perbandingan Luas ruang kerja : luas lantai : 1: 4 Oksigen di ruang kerja = (15 – 20) % udara Inhalasi manusia = 30 m3/hari atau = 44,14 ft3/jam ETAPRIMA SAFETY ENGINEERING, M.ARIEFF.L
Contoh -1 DISAIN SISTIM VENTILASI PENGENNCERAN UDARA Diketahui : Dimensi ruang (P X L X T ) = 40 x 30 x 3,5 m ; Standar flowrate (Q) = 20 cfm/person Standar flowrate difusser : (50- 100) fpm ; Dimensi Diffuser (40 cm x 40 cm ) x 20 % Standar exhaust : (20 cm x 20 cm ) x 50 % standar ruang kerja 4 M2/person Jam kerja : 8 jam /hari Perbandingan Luas ruang kerja : luas lantai : 1: 4 ETAPRIMA SAFETY ENGINEERING, M.ARIEFF.L Hitung : 1) Berapa jumlah orang yg ideal bekerja dalam ruangan ? 2) Berapa kebutuhan udara segar/fresh air bagi karyawan (M3/jam) 3) Berapa jumlah diffuser diperlukan ? 4) Berapa jumlah Exhaust dibutuhkan ? 5) Berapa % tase exhaust air yang ideal diperlukan ?
Jawab : Vol ruang = 40x30x3.5= 4200 M3 Luas = 40 x 30 = 1200 M2 Luas tempat kerja : ¼ x 1200 M2 = 300 M2 . Jumlah karyawan : 300: 4 = 75 orang Kebutuhan udara segar : 75 x 20 cf/min = x 60 min = 90.000 cfm = 2548.5 M3/jam 3) Kebutuhan jumlah diffuser : Dimensi diffuser : ( 0.4 x 0.4 ) M2 x 0.2 = 0.032 M2 ; V diffuser : 75/3.28=22.86 m/min ; flow rate difusser = A x V = 0.032 x 22.86 = 0.73 M3 x 60 min/jam = 43.89 M3 /jam Jumlah diffuser : 2548.5/43.89 = 58 buah. ETAPRIMA SAFETY ENGINEERING, M.ARIEFF.L
Kebutuhan exhaust : 30 % = 0.3 x 58 = 18 buah Flowrate exhaust` = kebutuhan udara segar/Jmlh exhaust Flowrate exhaust : 2548.5/18 = 141.58 m3/jam; Dimensi exhaust = (0.2 x 0.2 ) x50% = 0.02 M2 . Velocity exhaust = 141.58/0.02 = 7079 m/jam = 118 m/min. 6). Pertukaran udara = Volume ruang/kebutuhan udara segar Pertukaran udara : 4200: 2548.5 = 1.65 jam ( satu kali pertukaran udara) 7) Exhaust Air : Exhange rate : 2548.5/4200 x 100 % = 60 % ETAPRIMA SAFETY ENGINEERING, M.ARIEFF.L
Contoh -2 DISAIN SISTIM VENTILASI PENGENNCERAN UDARA Jumlah tenaga kerja 40 orang Standar flowrate (Q) = 20 cfm/person Standar flow rate ( 50-100) fpm pada diffuser. Dimensi diffuser (0.4 x0.4)m2 x 20% Standar exhaust : (0.20 X 0.20 ) M2 x 50 % Standar ruang kerja : 4 M2/person Standar perbandingan ruang kerja : luas ruang : 1: 4 Jumlah Exhaust : 40 % jumlah diffuser Tugas Buat Disain Ventilasi Umum 1) Berapa kebutuhan total ruang kerja ? 2)Berapa area ruang yang ideal ? Berapa tinggi ruang ? 3)Berapa jumlah diffuser yg diperlukan dan dimensinya ? 4)Berapa jumlah exhaust yg diperlukan dan dimensinya? 5)Berapa % tase exhaust air yg ideal ? ETAPRIMA SAFETY ENGINEERING, M.ARIEFF.L
Contoh -3 DISAIN SISTIM VENTILASI PENGENNCERAN UDARA 1. Jumlah Karyawan = 50 orang 2. luas lantai 1000 M3 ; tinggi ruang kerja : 3.25 m 3. Standar flowrate (Q) = 20 cfm/person 4.Standar flow rate ( 50-100) fpm pada diffuser. 5.Dimensi (0.4 x0.4) M2 x 20% 6.Standar exhaust : (0.20 X 0.20 ) M2 x 50 % 7.Standar ruang kerja : 4 M2/person 8. Jumlah Exhaust : 30 % jumlah diffuser 9. Standar Air supply : 20 cfm/person Tugas 1. Berapa jumlah diffuser ? 3.Berapa jumlah exhaust ? 2.Disain Berapa % -tase exhaust air rate actual ? ETAPRIMA SAFETY ENGINEERING, M.ARIEFF.L